Pole Mounted Circuit Breakers Automatic Circuit Reclosers Load Break Switches Feeder Terminal Units Fuse Cutouts Disconnect Switches Arrester Pole-Mounted Overhead Stations High Voltage Insulators
Pole Mounted Circuit Breakers Automatic Circuit Reclosers Load Break Switches Feeder Terminal Units Fuse Cutouts Disconnect Switches Arrester Pole-Mounted Overhead Stations High Voltage Insulators

12kV Intelligent Pole-Mounted Circuit Breaker (Magnetic Controlled)

ZNJWV1-12/Y630-20

12kV Intelligent pole-mounted magnetic controlled circuit breaker, three poles design, is mainly applicable for 12kV distribution network to interrupt the short circuit and earthing false, as demarcation switch, sectionalizer and connecting switch, also as outgoing switch in substation. Its breaking time is shorter than 10ms, which meets the demand of grade difference protection as high-speed switch. It can interconnect with the main station to realize distribution network automation, together with intelligent feeder terminal unit.

12kV Intelligent Pole-Mounted Circuit Breaker (Magnetic Controlled)

ZNJWV1-12/Y630-20

12kV Intelligent pole-mounted magnetic controlled circuit breaker, three poles design, is mainly applicable for 12kV distribution network to interrupt the short circuit and earthing false, as demarcation switch, sectionalizer and connecting switch, also as outgoing switch in substation. Its breaking time is shorter than 10ms, which meets the demand of grade difference protection as high-speed switch. It can interconnect with the main station to realize distribution network automation, together with intelligent feeder terminal unit.
12kV Intelligent Pole-Mounted Circuit Breaker (Magnetic Controlled)
12kV Intelligent Pole-Mounted Circuit Breaker (Magnetic Controlled)
12kV Intelligent Pole-Mounted Circuit Breaker (Magnetic Controlled)

Product introduction:

In the 12kV pole mounted magnetic controlled circuit breaker, we encapsulate the vacuum interrupter, main circuit live parts, high-accuracy voltage and current sensors, and high voltage pickup capacitors inside the cycloaliphatic-epoxy poles, based on decades of experience in solid insulation technology, eliminating all the partial discharge problems. The poles can pick up the voltage or current signals from power source side and secondary side at the same time, also the capacitor can power supply the intelligent electronic device (IED).

The three phases of the magnetic circuit breaker are driven by independent magnetic controlled mechanism respectively, which reduces dispersion, responding more timely and breaking more accurately. The breaking time is shorter than 10ms, which meets the demand of grade difference protection. The magnetic controlled circuit breaker is equipped with electrical latching and manual open handle, which latch electrically and manually the closing when the breaking handle is placed in the open position. 

Note: Technical datas and sketches are only for your reference. Such details in our contact prevail.


Model annotation:

image.png

Technical parameter:


NOItemUnitZNJWV1-12/Y630-20
1Interrupting medium-Vacuum
2Insulation medium-Solid insulation
3Rated voltage kV12
4Rated frequencyHz50
5Rated currentA630
6Rated short-time withstand currentkA25
7Rated short circuit breaking currentkA25
8Rated peak withstand currentkA63
9Duration of rated short circuit s4
10Interrupting times of short circuit currenttimes≥30
11Rated operation sequence-O-0.3s-CO-180s-CO
12Rated lightning impulse withstand voltage(1.2/50μs,peak)between phases, phase to earth kV75
between interrupters kV85
13Rated power frequency short-time withstand voltage (1min)between phases, phase to earth kV42
between interrupters kV48
14Partial discharge of the whole breaker(CS, VS and pickup capacitor are included)Testing voltagekV14.4
Partial discharge pC≤20
15Main resistanceμΩ≤80
16Mechanical operation lifetimeoperation≥20000
17Actuator type-Magnetic
18Operation type-Motor,with manually opening and closing
19Operation voltage VDC220
20Closing timems≤60
21Opening timems≤15
22Synchronism in closing and openingms≤2 
23Current sensors inside the poleRated current ratiophase sequence600A/1V
Zero sequence20A/0.2V
Accurancyphase sequencemetering 0.5s,Protection 5P10
Zero sequenceclass 1,Protection 10P10
Temperature range-40℃~70℃
Implementation-low power electro-magnetic
24Voltage sensors inside the poleRated voltage ratiophase sequence(10kV/√3)/(3.25V/√3)
Zero sequence(10kV/√3)/(6.5V/3)
Accurancyphase sequenceclass 0.5
Zero sequenceclass 1
Temperature range-40℃~70℃
Implementation-capacitor divider
Sampling type-power side and load side voltage pickcup
25Capacitors inside the polepower supply-built-in capacitor power supply
Installation -capacitor power supply integrated in the pole
Single-phase rated output powerW≥10±10%
26Remote/Local lockout-optional
27Re-close function-N/M
28Manually close lockout-N/M
29Closure protection level-not lower than IP67
30Circuit breaker liftimeYear20


Appearance size:

image.png


Installation indication:

image.png