All-Enclosed Pole-Mounted Overhead Station (New-Built Project)

The new-built project is to connect the overhead station components (such as circuit breakers, fuse cutouts, disconnect switches and arresters) to be a whole part by fast plug-in connection, while the connecting cables are prefabricated in our factory.

All-Enclosed Pole-Mounted Overhead Station (New-Built Project)

The new-built project is to connect the overhead station components (such as circuit breakers, fuse cutouts, disconnect switches and arresters) to be a whole part by fast plug-in connection, while the connecting cables are prefabricated in our factory.
All-Enclosed Pole-Mounted Overhead Station (New-Built Project)
All-Enclosed Pole-Mounted Overhead Station (New-Built Project)
All-Enclosed Pole-Mounted Overhead Station (New-Built Project)
All-Enclosed Pole-Mounted Overhead Station (New-Built Project)
All-Enclosed Pole-Mounted Overhead Station (New-Built Project)
All-Enclosed Pole-Mounted Overhead Station (New-Built Project)
All-Enclosed Pole-Mounted Overhead Station (New-Built Project)

Product introduction:

10kV All-enclosed pole-mounted Overhead Station is designed in the principle of standard design, independent function module, and flexible equipment replacement, integrating high voltage unit, transformer unit and low voltage unit. It features as high reliability, low construction cost, easy operation and maintenance, standardized and flexible components. It meets the development trend of the construction of international high-level distribution network lines and it is of great significance to improve the quality of power distribution network and work efficiency.

Note: Technical datas and sketches are only for your reference. Such details in our contact prevail.

Technical parameter:


Disconnet switch
Technical data
TypeRated voltage(kV)Rated current(A)1min power frequency withstand voltagelightning impulse withstand voltageRated short-time withstand  current(kV/S)Rated peak withstand current(kV)
Phase to phase and phase to ground(kV)Between contacts(kV)Phase to phase and phase to ground(kV)Between contacts(kV)
GFW1-12/S630-2012630505512513020/450


Fuse cutout
technical data
TypeRated voltage(kV)Rated current(A)1minpower frequency withstand voltageLightning impulse withstand voltageRated breaking current
(kA)
Insulator material
Phase to phase and phase to ground(kV)Between contacts(kV)Phase to phase and phase to ground(kV)Between contacts(kV)
GHRW12-100/12.512100505812513012.5Polymer


Circuit Breaker
Technical data
NOItemUnitData
1Rated voltagekV12
2Rated currentA630
31min power frequencydry:Phase to phase, phase to ground/ between contactskV42/48
4wet:Phase to phase, phase to ground/ between contactskV42
5Lightning impulse withstand voltage(peak)Phase to phase, phase to ground/ between contactskV75/85
6Rated short circuit breaking currentkA20
7Rated short circuit closing current, peakkA50
8Rated peak withstand currentkA50
9Short-time withstand current,4skA20
10Rated operation sequence-open-0.3s-close, open-180s-close, open
11Interrupting times of short circuit current30
12Mechanical operation lifetime10000
13Clearance between open contactsmm9±1
14Over travelmm3±1
15Closing trip time of contactsms≤2
16Three-phase contacts synchronism in closing and openingms≤2
17Circuir resistance on each phaseµΩ≤80
18Phase distance(interrupter side)mm300
19Current sensor-60A/0.176V


Lightning Arrester
Technical data
TypeRated voltage
(kV)
Continuous operating voltage
(kV)
DC Voltage reference (1mA)     
(kV)
Nominal  current
(kA)
Residual voltage≤(kV)4/10μs high current impulse withstand current 
(kA)
2ms Impulse rectangular current
(A)
1/10 steep wave impulse current8/20lightning impulse current30/60 operating impulse current
HY10WZ-17/451713.6241051.84538.3100400



Cables with insulation plugs
TypeRated voltage(kV)Rated current(A)Rated cross-sectional area(mm2)Material of cable coreThickness of sleeve(mm)
JK-10 1×501240050Copper5



Appearance size: