Pole Mounted Circuit Breakers Automatic Circuit Reclosers Load Break Switches Feeder Terminal Units Fuse Cutouts Disconnect Switches Arrester Pole-Mounted Overhead Stations High Voltage Insulators
Pole Mounted Circuit Breakers Automatic Circuit Reclosers Load Break Switches Feeder Terminal Units Fuse Cutouts Disconnect Switches Arrester Pole-Mounted Overhead Stations High Voltage Insulators

38kV Pole-Mounted Automatic Circuit Recloser

ZWM-38/800-16

38kV Pole-mounted automatic circuit recloser has three poles and permeant magnetic actuator. It is designed and tested according to standard IEC62271-111, mainly for 38kV distribution network to interrupt the short circuit and earthing false. Its breaking time is shorter than 10ms, which meets the demand of grade difference protection as high-speed switch. It can interconnect with the main station to realize distribution network automation, together with intelligent feeder terminal unit.

38kV Pole-Mounted Automatic Circuit Recloser

ZWM-38/800-16

38kV Pole-mounted automatic circuit recloser has three poles and permeant magnetic actuator. It is designed and tested according to standard IEC62271-111, mainly for 38kV distribution network to interrupt the short circuit and earthing false. Its breaking time is shorter than 10ms, which meets the demand of grade difference protection as high-speed switch. It can interconnect with the main station to realize distribution network automation, together with intelligent feeder terminal unit.
38kV Pole-Mounted Automatic Circuit Recloser
38kV Pole-Mounted Automatic Circuit Recloser
38kV Pole-Mounted Automatic Circuit Recloser

Product introduction:

In the 27kV pole-mounted automatic circuit recloser, we encapsulate the vacuum interrupter, main circuit live parts, high-accuracy voltage and current sensors, and high voltage pickup capacitors inside the cycloaliphatic-epoxy poles, based on decades of experience in solid insulation technology, eliminating all the partial discharge problems. The poles can pick up the voltage or current signals from power source side and secondary side at the same time, also the capacitor can power supply the intelligent electronic device (IED). 

The three phases of the automatic circuit recloser are driven by independent magnetic mechanism respectively, which reduces dispersion, responding more timely and breaking more accurately. The breaking time is shorter than 10ms. The recloser is equipped with electrical latching and manual open handle, which latch electrically and manually the closing when the breaking handle is placed in the open position. A mechanical counter is installed at the bottom of the switch for counting the number of switch operations.

Note: Technical datas and sketches are only for your reference. Such details in our contact prevail.


Model annotation:

型号注解英文.png

Technical parameter:


NOItemUnitZWM-38/800-16
1Interrupting medium-Vacuum
2Insulation medium-Solid   insulation
3Rated voltage kV38
4Rated frequencyHz50/60
5Rated currentA800
6Rated short-time withstand currentkA16
7Rated short circuit breaking currentkA16
8Rated peak withstand currentkA41.6
9Duration of rated short circuit s3
10Interrupting times of short circuit currentTimes≥30
11Rated operation sequence-O-0.5s-CO-2s-CO-2s-CO-2s-CO
12Rated lightning impulse withstand   voltage(1.2/50μs,peak)between   phases, phase to earth kV170
between interrupters kV170
13Rated power frequency short-time withstand   voltage (1minbetween   phases, phase to earth kV70
between interrupters kV70
14Partial   discharge of the whole breaker(CS, VS and pickup capacitor are included)Testing   voltagekV24.2
Partial discharge pC≤20
15Main resistanceμΩ≤80
16Mechanical operation lifetimeOperations≥10000
17Actuator type-Magnetic
18Operation type-Motor,with   manually opening and closing
19Operation voltage VDC380
20Closing timems60
21Opening timems10
22Synchronism in closing and openingms≤2 
23Current sensors inside the poleRated   current ratiophase   sequence1000A/1A
Accurancyphase   sequenceclass   0.5
Temperature range-40℃70℃
Implementation-electro-magnetic
24Voltage sensors inside the poleRated   current ratiophase   sequence(33kV/√3)/
    (3.25V/√3)
Accurancyphase   sequenceclass   1
Temperature range-40℃~70℃
Implementation-capacitor   divider
Sampling type-power   side and load side voltage pickcup
25Opening   lockout-Included
26Closure protection level-not   lower than IP67
27Circuit breaker liftimeYear20


Appearance size:

38kV柱上自动重合器外观尺寸图.png

Installation indication:

安装示意图.png